8100-0114 & 8100-0114-LF SETUP PROCEDURE |
| Print |
|
E-mail
|
Step 1 Hold set for 5 seconds, til reads ModE) Press SET 1 times to where it says LCK change to 1000 Press set one time to return to operaters menu Hold set for 5 sec, to read ModE set & reset button 3 seconds Cod has 0001 SET 6 times to MS change to 1111 Press Set Set and reset button for 2 seconds-go to Operators Menu
SET OPERATING MODE Hold set 5 sec, to read ModE Set to reflow, using up / down arrows (Reflow is T1) Press set one time to LCK Set to 1000 Press set one more time to return to Operators Menu
Press set & reset button for 2 seconds to get to Parameter Setup PARAMETER SETUP
Press "Set" to AL1 625 F or 300 C Press "Set" to P 90 F or 60 C Press "Set" to I 0004 Press "Set" to d 0001 Press "Set" to Ar 0010 Press "Set" to T 0002 Press "Set" to Pb 0000
Press "Set" to InP 0000 for APE Thermocouple (8100-0200-uni ) Press "Set" to UnIT 0000 for C or 0001 for F
Press "Set" to A S I 0001 Press "Set" to TLMT 0010 Press "Set" to CODE Set to 0000 Press Set & reset for 3 sec to operators menu
Set Profile 1 Set Point/Ramp Time
Press "Set" two seconds to SVI 250 for C, 475 for F
Press "Set" to RMP 00.00 Press "Set" two seconds to Operators menu
SET ADD TIME
Set to ProF 0001 Set to Tim 00.00 Set to AddT On Set to ADDT 0010 Set to Operators Menu
SET PROFILE 2 SETTIME POINT/RAMP
Set to ProF 0002 Set two seconds to SV2 475 for F, 250 for C Set to rmP2 01.00
Set key 2 sec to operators menu
SET PROFILE 3 SET POINT/RAMP TIME
Set to ProF 0003 Set 2 seconds to SV3 475 F or 250 C Set to rmP3 03.00 Set 2 seconds to Operators menu
SET PROFILE 4 SET POINT/RAMP TIME
Set to ProF 0004 Set 2 seconds to SV4 475 F or 250 C Set to RMP4 05.00
Set 2 seconds to Operators Menu Press "Set" to ProF 0001 Press "Set" 4 times to operators Menu
SET RAMP/SOAK SET POINTS/TIMES
Press "Set" 5 sec till ModE Change to ramp Press "Set" twice to return to operators menu
SET PROFILE 1
Press "set" to Ptrn 0001 Press "Set" 2 Seconds to L1-1 250 C or 475 F Press "Set" to T 1-1 01.00 Press "Set" to L 1-2 250 C or 475 F Press "Set" to T 1-2 02.00 Press "Set" and set the rest of the settings in profile 1 to 0000 Press "Set" to EndP 0000 Press "Set" 2 seconds to Operators Menu
Set Profile 2
Press "Set" tp Ptrn 0002 Press "Set" 2 seconds to L2-1 525 F or 275 C Press "Set" to T2-1 01.30 Press "Set" to L2-2 525 F or 275 C Press "Set" to T2-2 02.00 Press "Set" to L2-3 And set the rest of profile 2 to 0000 Press "Set" to EndP 0000 Set 2 seconds to operator Menu
SET PROFILE 3
Press "Set" to Ptrn 0003 Press "Set" 2 seconds to L3-1 300 F or 150 C Press "Set" to T 3-1 00.45 Press "Set" to L 3-2 300 F or 150 C Press "Set" to T 3-2 01.00 Press "Set" to L 3-3 400 F or 200 C Press "Set" to T 3-3 00.45 Press "Set" to L 3-4 400 F or 200 C Press "Set" to T 3-4 00.45 Press "Set" to EndP 0004 Press "Set" 2 seconds to Operators Menu
SET PROFILE 4
Press "Set" to Ptrn 0004 Press "Set" 2 seconds to L4-1 475 F or 250 C Press "Set" to T4-1 00.20 Press "Set" to L4-2 475 F or 250 C Press "Set" to T4-2 01.00 Press Set and set the rest of Profile 4 to 0000 Press "Set" to EndP 0000 Press "Set" 2 seconds to Operator Menu
Press "Set" to Ptrn 0001
Press "Set" twice to STOP
SET TO MANUAL MODE
Press "Set" 5 seconds to ModE
Press up or down arrow to select Man Mode.
Press up and down arrow togethor to flash "This resets the timer"
Setup is Complete
|